UX90-006M - Occupancy/Light Data Logger (Expanded Memory)

R3,816.69

The HOBO Occupancy & Light data logger monitors room occupancy and indoor light changes to identify occupancy patterns and determine energy usage and potential savings. The HOBO UX90-006 Room Occu..

  • Brands ONSET
  • Product Code: UX90-006M
  • Availability: 7-10 Days

Tags: occupancy, light, data, logger, ux90-006m, expanded, memory, hoboware, usb

UX90-006M - Occupancy/Light Data Logger (Expanded Memory)

The HOBO Occupancy & Light data logger monitors room occupancy and indoor light changes to identify occupancy patterns and determine energy usage and potential savings. The HOBO UX90-006 Room Occupancy/Light Data Logger is available in a standard 128 KB memory model (UX90-006) capable of 84,650 measurements and an expanded 512KB memory version (UX90-006M) capable of over 346,795 measurements.


Highlighted Features

  • Measures room occupancy up to 12 meters away
  • Auto-calibration of ON and OFF thresholds ensures reliable readings
  • The LCD screen displays signal strength, enabling proper logger placement
  • Highly recommended light pipe accessory eliminates effects of ambient light to ensure the most accurate readings
  • Compatible with HOBOware and HOBOware Pro software for logger setup, graphing and analysis


In what environment does this data logger operate?

This data logger operates in an indoor environment.

What measurements does this data logger support?

The UX90-006M data logger supports the following measurements: Light On/Off and Occupancy


For more information visit Onset

The following are associated resources for this product. In general users of this product can gain insight into its possible use by utilizing the resources below.


White Papers

On-Demand Webinars

How-To Videos

Informational Pages

Application Stories

Tech Notes

Self-Guided Training

Choosing an Occupancy and Light On/Off Data Logger – 5 Important Considerations
Tips, Tricks, Methods for Industrial Data Logging
Combining Plug Load and Occupancy Data in HOBOware Pro
Tips on Buying a Data Logger
Data Loggers Investigate Energy Waste in Indiana School District
Data Assistant Videos on YouTube
Working with UX90 Time-of-Use Loggers

Data Logger Basics
HOBOware Menus Explained Part 1
What is a Data Logger?
Energy Performance Monitoring - Roundtable Discussion
The data logger is shutting off prematurely


HOBO UX90 Time-of-Use Data Loggers
HOBOware Menus Explained Part 2

Industry Viewpoint: Energy Assessments Using Data Loggers
Data loss and recovery


Tips for Selecting and Deploying Data Loggers for Building Performance Monitoring
How to add graph labels in HOBOware Pro

Monitoring Building Efficiency with Data Loggers: a Conversation with Darren Goody
Drying a wet circuit board



How to analyze data from the HOBO UX90-005 and 006 data loggers

Occupancy Loggers Drive Cost-Saving Decisions in Historic San Francisco Building
Event data logging vs State data logging



How to Analyze HOBO UX90-005 & UX90-006 Light/Occupancy Data

Turning Buildings Green with Data Loggers: a Conversation with Alexander E. Othmer
How do I delete, erase, or clear data from my data logger's memory?



How to automatically launch multiple HOBO USB data loggers


Logger power failure and data loss



How to automatically readout and save data from a HOBO USB data logger


Logging Duration in the Launch Screen- What Does That Mean?



How to configure the HOBO UX90-005 and 006 data loggers



Sample Data - HOBO UX90-005 & -006 Light On/Off & Occupancy - Light Sensor Internal Calibration Event


  • HOBO UX90-006M Occupancy/Light Data Logger
  • Command™ strip
  • Double-sided tape
  • Hook & loop strap

Light Sensor
Light Threshold > 65 lux
Light Type LED, CFL, fluorescent, HID, incandescent, natural
Logger
Download Type USB 2.0 interface
LCD LCD is visible from: 0° to 50°C (32° to 122°F); the LCD may react slowly or go blank in temperatures outside this range
Logger Battery Life 1 year typical use
Logger Environmental Rating IP50
Logger Operating Range Logging: -20° to 70°C (-4° to 158°F); 0 to 95% RH (non-condensing) Launch/readout: 0° to 50°C (32° to 122°F) per USB specification
Logger Size 3.66 x 8.48 x 2.87 cm (1.44 x 3.34 x 1.13 in.)
Logger Time Accuracy ±1 minute per month at 25°C (77°F)
Memory Modes 128 KB (84,650 measurements, maximum)
Occupancy Sensor
Detection Performance 102° (±51°) Horizontal; 92° (±46°) Vertical
Detection Range maximum 12 m (39.4 ft
Detection Zones 92